Float Installation Details
• Verify that the color of the water float agrees with the
product to be used within the storage tank (Figure 1).
• Use a small flat bladed screwdriver to pry-off / remove
the E-Ring from the bottom of the probe shaft. Then
remove either the stainless steel float retainer washer or
the plastic bottom mount retainer. See Figure 2.
• Install the floats per Figure 2. Product float first (magnet
end up) and then the water float (magnet end up).
• Install the stainless steel, “float retainer” washer at the
bottom of the probe shaft. Slide the E-Ring into the
grove below the stainless steel washer. See Figure 2.
• Install the TSP-K4A riser cap adapter per installation
guide (part number 000-0078).
• Install, wire, and test the TSP-LL2 liquid level probe. See
your installation guide.
Figure 2:Float & Retainer Installation Detail
E-ring
E-ring
Bottom View of
Probe Shaft
Showing Stainless
Steel Washer and
E-ring Retainer
Stainless Steel Washer
Stainless
Steel Washer
End of
Probe Shaft
Probe Shaft
Float
Retainer
Detail
Product Float
(Magnet End Up)
Water /Interface Float
(Magnet End Up)