Franklin Fueling Systems TS-RA2 User Manual
Page 9
9
If a Rule is not already in the system for the alarm you
need, Click on the to Select or create a rule for the Tank
Overfill Alarm.
Select Events
After selecting Events / Event, the following screen shows
the setup for the alarm.
The code could be either High product level or High
product Volume depending on the choice under the Fuel
Management System High Product Limit. Choosing the
incorrect code will lead to the rule not functioning as
designed.
Navigate back to the Rules setup page and select Actions,
and set the relay to activate.
Navigate back to the Rules / Actions page and add another
action.
Set this up the same as the previous screen, but have the
action set to deactivate. This will allow the relay to reset
(the alarm will continue until it is acknowledged).