TS-TPI Installation and Wiring Guide

Stand AloneTS-TPI with TPCs

●

Communication between TS-TPI and TPCs. Use this application for remote
controller fault indication and controller fault reset.

●

Stand Alone TS-TPI requires separate 120 - 240 vac, 50/60 hz, power

●

TS-TPI reset switch will reset the TS-TPI in the event of a communication conflict.

●

The TPC fault reset will reset a pump controller that is in a fault conditon. It will
only reset controllers that are indicating a fault alarm. If none of the controllers are
in alarm no reset will take place.

●

Alarm Silence button will silence the audible alarm but not clear the fault.

●

Connect TPCs so all Stand alone TPCs are on the same port and Master/Slave
configured units are on their own port. Address TPCs so controllers on same port
have unique addresses.

STAND ALONE TS-TPI

T

X

D

4

85-

GN

D

R

X

D

485+

T

X

D

485

-

GN

D

R

X

D

485+

T

X

D

4

85-

GN

D

R

X

D

485+

T

X

D

4

85-

GN

D

R

X

D

485+

T

X

D

4

85-

GN

D

R

X

D

485+

HOS

T

POR

T

PO

R

T

1

PO

R

T

2

PO

RT 3

PO

R

T

4

ADDITIONAL TPC
GROUPS

RE

D

WH

IT

E

BL

AC

K

CABLE-BELDEN CONDUCTOR
#9365-18AWG OR EQUIVALENT

+ G

RS485

TPC

CONTROLLERS MAY INCLUDE THE
MagVFC, STP-SCI, STP-SCIII, IST-VFC
AND STP-SC

ADDITIONAL
TPC CONNECTIONS

RED
WHITE

BLACK

GND L2/N

L1

INPUT POWER

SPECIFICATIONS
Input power:
120 - 240 Vac 50/60 hz

Indoor installation only.
Operating temperature:
40 - 105° F (4 - 41° C)

TS-TPI
RESET

TPC FAULT
RESET

ALARM
SILENCE

Figure 2-6