3operation – Alpha Technologies CFR Redundant Control Unit User Manual

Page 13

Advertising
background image

11

3

Operation

3.1

RCU Start–Up and Test Procedure

Switch the Input 1 circuit breaker ON.

The Input 1 LED lights, showing the return of primary power. The RCU transfers back to
Input 1 after about 30 seconds, after the voltage and frequency stabilizes. When done, the
Contactor 1 LED turns ON.

Turn ON
Input 1 circuit breaker

Contactor 1 LED

Input 1 LED

Figure 3.3

Return Primary Power

1

STEP 3: Restore Primary Power

Switch the Input 2 circuit breaker OFF.

The Input 2 LED on the front panel turns OFF, indicating the loss of secondary power.
There should be no transfer or any other change in the status of the RCU.

Switch the Input 2 circuit breaker ON to return to normal status.

STEP 4: Test Secondary Power

Turn OFF
Input 2 circuit breaker

Figure 3.4

Test Secondary Power

Input 2 LED

1

2