Maintenance, 1 internal fuse replacement, 4maintenance – Alpha Technologies CFR Redundant Control Unit User Manual

Page 17

Advertising
background image

15

4

Maintenance

4.1

Internal Fuse Replacement

DANGER: Fuse replacement should be done only by qualified personnel.

DANGER: Make sure the power is OFF before opening the front panel.

Two fuses are located on the power board: Input 1: F1 and Input 2: F2 (both are 500 mA).

Figure 4.1

Power Board Fuse Location

R 10

120 V

120 V

R 9
R 8

R 1

R 2

R 3

R 4
R 5
R 6

R 7

208 V

or

240 V

208 V

or

240 V

R 11
R 12

F 2

F 1

1

1

2

2

3

3

4

4

5

5

J 1

J 2

1

2

34

56

7

8

J 3

Input 1 Fuse
(500 mA)

Input 2 Fuse
(500 mA)

The RCU has four internal fuses that are accessible from the front panel.

To lower the front panel:

Switch OFF the Input 1 and 2 circuit breakers.

Remove the two Phillips screws on the RCU front panel.

Carefully lower the front panel forward 45 degrees.

1

2

3

Figure 4.2

Logic Board Fuse Location

Logic Board

K1

K3

F2

3.15 Amp

F1

3.15 Amp

Two fuses are located on the logic board: Contactor 1: F1 and Contactor 2: F2 (both are
3.15 Amps).