2 a tour of the rcu – Alpha Technologies CFR Redundant Control Unit User Manual

Page 4

Advertising
background image

1.2

A Tour of the RCU

1

Introduction

1.2.1

Front Panel (Figure 1.2)

Input 1 LED:
Shows the presence of AC power at Input 1.

Input 2 LED:
Shows the presence of AC power at Input 2.

Contactor 1 LED:
Shows Contactor 1 is closed, providing primary power to the output.

Contactor 2 LED:
Shows Contactor 2 is closed, providing secondary power to the output.

Output LED:
Shows there is power at the output.

Manual Transfer LED:
Shows both primary and secondary power sources are in phase and that a manual transfer
can be done with the make–before–break manual bypass switch.

Red Alert LED:
Shows that one of the contactors or the control logic has failed.

Input 1 Circuit Breaker:
Provides circuit breaker protection to the primary input and acts as an ON/OFF switch.

Input 2 Circuit Breaker:
Provides circuit breaker protection to the secondary input and acts as an ON/OFF switch.

Select 1 Switch:
Opens the secondary contactor before closing the primary to provide Input 1 power to the
output.

Select 2 Switch:
Opens the primary contactor before closing the secondary to provide Input 2 power to the
output.

Purpose: Describes the RCU’s controls, displays and terminal blocks