Alpha Technologies CFR 1500, CFR 2000, CFR 2500, CFR 3000 User Manual

Page 10

Advertising
background image

1.2 The CFR Advantage,

continued

COMMUNICATIONS AND INTELLIGENCE

Alpha's interchangeable Standard Interface Device and Intelligent Interface

Device allow your CFR to become an active part of your communications network
providing you with a variety of interface options.

SELF-TEST CAPABILITIES

The CFR has a built-in, self-test function that checks all critical areas of the

UPS, including the batteries, to ensure optimum performance. Whenever a problem
is detected, the UPS lights a “Service” indicator. Self-test is extremely useful during
troubleshooting and maintenance.

PRECISE LOAD & OVERLOAD INFORMATION

The Alpha CFR provides vital load information to eliminate guess work associ-

ated with matching the appropriate load to your unit. The Alpha CFR displays the
existing load and, whenever the load exceeds the rated output, an "Overload"
indicator is illuminated.

GENERATOR READY

The CFR UPS is equipped with a frequency sense circuit, along with a constant

slew frequency synchronization circuit, to provide trouble-free operation with most
standby generators.

SAFETY

Designed to meet or exceed the safety standards established by UL, CSA and

VDE, the Alpha CFR UPS is one of the safest, most reliable and versatile
uninterruptible power supplies available. Our commitment to safety and quality
engineering has not only established industry-wide safety standards, but has earned
Alpha Technologies international recognition as a leader in power protection
equipment.

1. INTRODUCTION

3

6. MAINTENANCE

62

SYMPTOM

CAUSE

REMEDY

Fast Detector / Low
Sensitivity Fault.

PLL Fault.
Instability in line freq
from generator; or out of
phase wiring.

High Ambient Temp.
Caused by excessive
load or heat source.

Output Voltage High.
Calibration problem or
incorrect jumper setting
on power board.

Output Shorted

or

Output Voltage Low

or

Output Voltage Failure.

PWR BRD Fault or
-5 VDC Failure.

PWR BRD EPROM
Failure.

Self-Test Failure.

Battery Over-Voltage
or Charger Fault.

6.7

Troubleshooting Using the SID,

continued

OVERLOAD LED (ON)
SERVICE LED (ON)
ALARM OFF switch
pressed and held:

100% LED (Flashing)
SERVICE LED (ON)
ALARM OFF switch
pressed and held:

100% LED (ON)
SERVICE LED (ON)
ALARM OFF switch
pressed and held:

75% LED (Flashing)
SERVICE LED (ON)
ALARM OFF Switch
pressed and held:

75% LED (ON)
SERVICE LED (ON)
ALARM OFF Switch
pressed and held:

50% LED (Flashing)
SERVICE LED (ON)
ALARM OFF Switch
pressed and held:

50% LED (ON)
SERVICE LED (ON)
ALARM OFF Switch
pressed and held:

25% LED (Flashing)
SERVICE LED (ON)
ALARM OFF Switch
pressed and held:

25% LED (ON)
SERVICE LED (ON)
ALARM OFF Switch
pressed and held:

Call Alpha.

Wait for line power to
return.

Check wiring.

Reduce ambient
temperature. Alarm
will reset when temp
returns to safe level.

Contact Alpha.

Check load

Contact Alpha.

Contact Alpha.

Contact Alpha.

Check batteries and
retest unit. Contact
Alpha if unit continues
to fail.

Contact Alpha.