3.2.1 Terminal Block Input and Output

CAUTION

:

Installation and wiring should be performed by qualified service personnel

in accordance with applicable electrical codes. Verify that the main utility panel is
switched OFF before proceeding. Mark all circuit breakers supplying the UPS.

1.

Connect the input and output wires (Refer to the table below for
recommended wire sizes and tightening torques.)

3. INSTALLATION

Fig. 10

CFR 1500, CFR 2000, CFR 2500,

and CFR 3000 Rear Panels

UPS

Receptacle

BATTERY

Circuit Breaker

AC LINE

Power Cord

GROUND Lug

AC LINE

Circuit Breaker

MODEL

TERMINAL BLOCKS TIGHTENING TORQUE

AWG

mm

2

Inch

Newton

Pounds

Meters

1500-2500 (60Hz)

14

2.0

35

4.0

3000 (60Hz)

12

3.0

35

4.0

2000-3000 (50Hz)

16

1.5

35

4.0

Leveling Feet

(CFR 3000 only)

5.10 Maintenance Parameters,

continued

5. RS-232 TERMINAL COMMUNICATION

Slow Detect Hi Ref

Increasing this value will make the UPS more sensitive to a slow,

high amplitude line disturbance (sustained overvoltage) by lowering the
overvoltage detection level.

NOTE: The Slow Detect Hys Hi Ref should also be adjusted by the
same amount.

Slow Detect Hys Lo Ref

Increasing this value will raise the voltage level at which the UPS

will

resume LINE POWER operation after a line disturbance has been

corrected. This setting should normally be 1 - 3 settings

above the

Slow Detect Lo Ref setting.

Slow Detect Hys Hi Ref

Increasing this value will lower the voltage level at which the UPS

will

resume LINE POWER operation after an overvoltage condition has

been corrected. This setting should normally be the same, or 1 - 3
settings

above, the Slow Detect Hi Ref setting.

Max. PLL Slew Rate

Increasing this value will reduce the speed at which the Phase

Locked Loop (PLL) will change the output frequency while the UPS
resumes LINE PRESENT operation after a line fault has been cor-
rected. It will also increase the time required to resume LINE
PRESENT operation.

Battery Warning Ref

Increasing this value will increase the time before a LOW

BATTERY WARNING occurs, thus allowing the batteries to drain more
of their charge before a warning is given. Decreasing this value will
allow more run time between LOW BATTERY WARNING and SHUT-
DOWN.