1. INTRODUCTION

The Alpha CFR-UPS

provides regulated, current-limited,

output with excellent isolation and noise attenuation.

1.1 The Alpha CFR

Congratulations on your purchase of one of the most advanced and intelligent

Controlled Ferroresonant-Uninterruptible Power Supplies (CFR-UPS) in the world! The
Alpha CFR is designed to keep your equipment operating, regardless of the condition
of your utility power. This means that your vital equipment will no longer be affected by
spikes, surges, sags, noise, brownouts, blackouts or other forms of electrical distur-
bances. Operation is as simple as plugging your equipment into the back of the UPS
and switching on the power.

The CFR provides you with a wide range of power management options using

your choice of interface devices. The Standard Interface Device displays vital UPS
operating parameters, including Alarms, and allows you to manually self-test the UPS.
The Intelligent Interface Device provides you with precise Voltage, Current and
Frequency information, plus maintains an on-going record of all Alarm and Line Failure
Events. As an active center of communication, your CFR can also be interfaced
directly to your computer system to inform you, and your users, of changes in status as
they occur.

With distribution networks and service centers located throughout the world,

Alpha Technologies is here to back you up. From your date of purchase, Alpha
provides complete technical support and prompt, reliable service to ensure that your
CFR-UPS provides you with a lifetime of reliable operation.

1

CFR

CFR

CFR

CFR

60 Hz Models

1500

2000

2500

3000

Output Power (VA)

1500

2000

2500

3000

Active Power (WATTS)

1125

1340

1670

2000

Input Voltage
(VAC)

120/208/240

120/208/240

120/208/240

120/208/240

Input Current
Max. (A)

12.0/7.4/6.4

14.6/8.4/7.3

17.6/10.2/8.8

21/12/11

Output Voltage
(VAC)

120/208/240

120/208/240

120/208/240

120/208/240

Battery Runtime

*

(Internal)

17

14

9

25

50 Hz Models
Output Power (VA)

N/A

2000

2500

3000

Active Power (WATTS)

N/A

1340

1670

2000

Input Voltage (VAC)

N/A

230

230

230

Input Current Max. (A)

N/A

7.6

9.0

10

Output Voltage (VAC)

N/A

230

230

230

64

7.1 Specifications

7. SPECIFICATIONS

Dimensions

CFR 1500, 2000, 2500: .......... 8.5"W x 21.3”H x 22.5"D

(216mm x 541mm x 571mm)

CFR 3000: .............................. 8.5"W x 21.3"H x 30"D

(216mm x 541mm x 762mm)

Weights

60 Hz Models

50 Hz Models

CFR 1500 ........... 160 lbs./72 kg ................. N/A
CFR2000 ............ 171 lbs./78kg .................. 174 lbs./79kg
CFR 2500 ........... 185 lbs./84kg .................. 191 lbs./87kg
CFR3000 ............ 283 lbs./128 kg ............... 289 lbs./131kg

Specifications subject to change without notice.

*Battery Run times are calculated at a typical load of 80%

NOTE: Specifications are at load and at temperature and based upon use with
computer-type loads with a crest factor of 3:1 max., and a typical power factor
of 0.75.