4.2 Using the Standard Interface Device

Fig. 17

Standard Interface Device

The Standard Interface Device displays vital UPS operating parameters and has

the ability to self-test the UPS at the touch of a button. When used in conjunction with
the CFR's rear-panel “Form-C” contact closures, UPS status information can be sent
directly to a Local Area Network (see section 2.5).

4. OPERATION

LINE PRESENT LED

Manual Start (Hold to Test) Switch

Alarm OFF Switch

LINE FAILURE LED

OUTPUT LOAD LEDs

TEST LED

LOW BATTERY WARNING LED

SERVICE LED

LOW BATTERY SHUTDOWN LED

5. RS-232 TERMINAL COMMUNICATION

37

5.4 Menu Commands Overview,

continued

Calibrating the CFR

The CFR-UPS may be calibrated using two sets of parameters - Maintenance

Parameters (commands “70” to “79”) and Service Parameters (commands “80” to
“89”). Maintenance parameters allow you to customize the CFR detection and
warning levels. There should be no need to change these setting unless wider or
narrower detection tolerances are required.

Transmitting Unsolicited Alarms

The UPS can automatically transmit alarm messages (in ASCII format) to notify

a status change or a power problem as it occurs. You can enable or disable this
option by using commands “510” and “509” respectively.

5.5 System Parameters

The “SYSTEM PARAMETERS” screen provides UPS battery temperature

information and manual initiation and termination of SELF TEST.

Battery Temperature
Displayed in degrees C, Ambient Temperature is measured inside the

UPS

in the vicinity of the battery compartment.

Start Test
Self Test can be initiated by selecting this menu. The test duration default
is 60 seconds.

Stop Test
Self Test can be terminated prior to the full duration of the test run time.