4.

OPERATION,

continued

4.2

Using the Standard Interface Device ............................. 28

UPS Powering Up
Output Shutdown Pending
Output Shutdown in Progress
Line Present Operation
Line Failure (AC Input Out of Tolerance)
Line Failure Operation
Line Synchronization
Low Battery Warning
Low Battery Shutdown
Test
Service
Alarm Off Switch
Manual Start / (Hold to Test) Switch
Output Load Display

5.

RS-232 TERMINAL COMMUNICATION ............................. 33
5.1

Remote RS-232 Operation ........................................... 33

5.2

RS-232 Menu Selection Icons ...................................... 34

5.3

Remote Terminal Quick Reference ............................... 35

5.4

Menu Commands Overview ......................................... 36

5.5

System Parameters ...................................................... 37

5.6

Input Parameters .......................................................... 38

5.7

Output Parameters ....................................................... 38

5.8

Battery Parameters ...................................................... 40

5.9

User Parameters .......................................................... 40

5.10 Maintenance Parameters .............................................. 45
5.11
Parameter DUMP Command ........................................ 47
5.12
Event Descriptions ....................................................... 48
5.13
RS-232 Terminal Setup ................................................ 52

6.

MAINTENANCE .................................................................. 53
6.1

CFR Maintenance ........................................................ 53

6.2

Battery Maintenance ..................................................... 53

6.3

Battery Testing ............................................................. 54

6.4

Removing the CFR Front Panel and Cover ................... 55

6.5

Internal Battery Replacement ........................................ 56

6.6

Troubleshooting Guide ................................................. 59

6.7

Troubleshooting Using The SID .................................... 61

6.8

Repair Instructions ....................................................... 63

6.9

Parts and Ordering Instructions .................................... 63

7.

SPECIFICATIONS .............................................................. 64
7.1

Specifications ............................................................... 64

8.

WARRANTY ........................................................................ 66

ii

The Alpha CFR

65

7.1 Specifications,

continued

Common Specifications

Input Frequency

60 Hz or 50 Hz (± 3%)

Input Voltage Variation

- 20% to + 10%

Output Frequency

± 0.1 Hz (inverter mode)

Output Regulation

± 1%

Efficiency @Typical Load

90%

Total Harmonic Distortion

< 5%

Output Waveform

Sine

Step Load Response

< 10% @ 100% load

Noise Attenuation

Common Mode

-120dB (100K - 1 MHz)

Normal Mode

-60dB (100K - 1 MHz)

Low Voltage Trigger

80% nominal voltage (adjustable)

High Voltage Trigger

110% nominal voltage (adjustable)

Batteries

Valve regulated, maintenance-free

Battery Voltage

48 VDC

Batt. Low Volt. Cutout

39 VDC (>25% load), [42 VDC (<25% load)]

Battery Recharge Time

5.0 hrs. for CFR 1500-2500
10 hrs. for CFR 3000

Charger

Linear

(3A max.)

Charger Voltage

55.2 VDC at 25°C (adjustable)

Operating Temp

32°-104° F / 0° - 40°C

Heat Output

574 BTU/h; 168 W

Audible Noise @ 1M

42dBA

Indicators

Line Present, Line Failure,
Low Battery Shutdown,
Low Battery Warning (LED / audible alarm),
Test, Service and Output Load

Controls

Manual Start / Test, Alarm OFF

Connectors

AC Input, AC Output, External Alarm;

Intelligent Interface Device and
External Battery

Output Alarms

Rear panel RJ-45 connector (Form C
contact closures rated 1A, 30V) for
Line Present / Line Failure, and
Battery OK / Low Battery Warning

Specifications subject to change without notice.

7. SPECIFICATIONS

IMPORTANT:

EMERGENCY SHUTDOWN PROCEDURE ON INSIDE BACK COVER