0700015-J0 Rev B

6.6 Alarms

This menu category consists of power system alarms. Parameters can be set/accessed such as power

system high/low voltage alarms, AC Mains high/low voltage alarms, Supervisor programmable alarms

and alarm tone enable (audible alarm buzzer).
All voltage-related alarms (HVA 1 and 2, LVA 1 and 2) are based on voltage readings taken from the ana-

log input channel for the power system’s BATTERY VOLTAGE.
See Table J for factory default settings.

6.6.1 Alarm Icons

LCD Symbol

Alarm

Web Symbol

Active alarm condition.

Alarm condition that has been silenced

Power system Major Alarm

Power system Minor Alarm

No Alarms

A power system Message alert.

Rectifier Information accompanied by the number of rectifiers in

the system
Power Save feature enabled and active accompanied by the

number of rectifiers shut down

6.6.2 Definitions

Major

Alarm conditions that are serious or an immediate threat to service. The red front

panel LED illuminates and the Major Alarm icon displays on the GUI

Minor

Alarm conditions of a less serious nature or not an immediate threat to service. The

yellow front panel LED illuminates and the Minor Alarm icon displays on the GUI.

Message

Non-audible, non-priority alert. No change in LED activity and the Message icon

displays on the LCD GUI. The Supervisor can define the condition(s) and set relays

to change.

Rectifier Major
Fail Count

Number of rectifiers that are in a fail condition resulting in a major alarm or an

immediate threat to service. Adjust this setting in the

Rect. Major Fail Count

alarm

submenu.

Rectifier Minor
Fail Count

Number of rectifiers that are in a fail condition resulting in a minor alarm or a non-

immediate threat to service. Adjust this setting in the

Rect. Minor Fail Count

alarm

submenu.

Rectifier Minor
Alarm

Alarm condition detected in a rectifier but not considered an immediate threat to the

operation of that rectifier.

Rectifier Fail
Alarm

Alarm condition detecting an actual rectifier failure.

ALCO

Alarm cutoff (see Section 4.5.1) may silence all ALCO enabled alarms and may

change relay state. For controls, the relay does not change state – only the audible

alert is silenced.