Section 6.5.4 – Alpha Technologies Cordex Controller Ver.3.1x User Manual

Page 54

Advertising
background image

0700015-J0 Rev B

52

6.5.4 Battery (Discharge) Test

The Battery Test (BT) is used to update the status of the battery capacity. It can be set to run automati-

cally or can be initiated manually (via the Mode Selection button). See 4.12 for more details.

BT End Voltage

BT Termination Voltage:

Controls the end (or termination) voltage of the BT; +0.5

V above Rectifier BT Voltage is recommended.

Rectifier BT Voltage:

Identical to the field of the same name in the Rectifier

configuration settings in 6.3.2 – a change in one alters the other. The Supervisor

can set the Rectifier BT Voltage to the desired value during the test (mode). This

setting should have a minimum of LVD + 1 V.

Rectifier BT Timeout:

Identical to the field of the same name in the Rectifier

configuration settings in 6.3.2 – a change in one alters the other. Controls the

duration of the Battery Test.

Auto BT

Set the

Interval

time, in days, between automatic battery tests.

Scheduled BT

Use the

Configure Schedule

button to set up a schedule.

Remote BT Mode

This feature will force a transition to BT mode when a user-defined condition

(custom alarm) is true.

Remote BT (Custom 1-20)

: This menu item enables the Supervisor to assign a

Custom Alarm number between 1 and 20. (Refer to 6.6.3 to configure custom

alarms.)
NOTE

: This feature is exclusive to the Cordex series of rectifiers. If Remote BT

is active and a rectifier other than the Cordex series is added to the system then

Remote BT will be aborted.

Battery Properties
(LCD only)

The

Battery Properties

button at the bottom of the window links to the Battery

Properties window (see 6.5.7). The return path is to the BT window.

Figure 53 — Battery Test - Web