0700015-J0 Rev B

74

6.7.2.6 Examples of Signal Configuration and Customization

Example One – Configure Signal and Customize Signal Equation
Select Custom Signal from the list and then tap the

Configure

button to produce another window and list

of items to navigate.
Use the pull-down menu to set the decimal precision or tap Customize to build a signal equation similar

to the equation shown in 6.6.5.7 Custom Alarms. See also 7.2 Equation Builder Keypads.
NOTE: Once a signal equation has been built – it can be edited or disabled – it cannot be removed.

Example Two – Configure AC Mains
Use the pull-down menu to set the decimal precision as shown in the following example:

Example Three – Configure (Battery Temperature sensors)
Use the pull-down menu to set the decimal precision and tap/toggle the check boxes to enable sensor(s)

for battery temperature as shown in the following example:

Example Four – Configure ADIO01 (Shunt MUX)
Configure the input range of each of 16 channels for the Cordex Shunt MUX as follows:

1. Select channel (CH15 in the example below) and then

Configure

.

2. The window changes to show a list (for review) of the input range of each channel. Multiple channels

can be selected for the new value. Select channels and then

Set Range

to configure (or select the

icon to accept the list and return to the previous window).

3. The virtual numeric keypad enables editing of the input range. Select the X icon to return to the

previous window or select the

√ icon to accept the new setting.

A message will indicate that the selected devices have been configured with the new setting. Select the

X icon to return to the first window.

Figure 77 — Controller Signals configuration example three (enable temperature sensors)

Set input range to shunt size

(in Amperes/50 mV)

Figure 78 — Controller Signals configuration example four (configure input range for Shunt MUX channels)

Figure 79 — Controller Signals configuration example two (set decimal precision)

nnnn

nnn.n

nn.nn

n.nnn