6.5.5 Boost (BST) Mode

This feature provides the supervisor with the means to equalize charge the battery at a higher voltage

relative to the connected load. The transition to BST mode occurs when a user-defined condition (custom

alarm) is false.
NOTE: Activation is manual and certain conditions must be met to prevent damage to the load.
A custom alarm must be created to include all the desired factors that must be taken into account before

activating BST mode. This mode is only permitted if the alarm is false.
Once activated, BST mode concludes with a timeout or whenever the status of the custom alarm is true

and reverts to FL mode. BST mode can also be cancelled if the conditions that are required in order to

activate BST mode have changed.

Enable

Sets the CXC Boost Mode feature

Voltage

Deviation of the Boost Mode voltage

Timeout

Duration of the Boost Mode

Inhibit

Assign a Custom Alarm number between

1 and 20. (Refer to 6.6.3 to configure

custom alarms.)

Battery Properties
(LCD only)

The

Battery Properties

button at the

bottom of the window links to the Battery

Properties window (see 6.5.7). The return

path is to the Boost Mode window.

6.5.6 Battery Current Termination (BCT) Equalize

Refer to Section 2.9.3 for an overview of this feature.
Since the BC Threshold is in amps, it has to be set with caution as the battery current input has limited

accuracy. If it is too low, the threshold may never be reached. The threshold should be at least twice as

large as the jitter on the battery current input. If this limitation forces the threshold to be set higher than

desired, the BCT Duration can be increased slightly to compensate.

Enable

Sets the CXC BCT Equalize feature

Duration

Duration of the BCT Equalize function

in hours

BC Threshold

Threshold (in amps) for the battery

charging current that will trigger the

BCT Equalize function

Battery Properties
(LCD only)

The

Battery Properties

button at the

bottom of the window links to the

Battery Properties window (see 6.5.7).

The return path is to the BCT Equalize

window.