Alpha Technologies Cordex Controller Ver.3.1x User Manual

Page 64

Advertising
background image

0700015-J0 Rev B

62

6.6.5 Menu Items for Configuring Alarms Associated with Each Analog Input

6.6.5.1 Current Alarms

Battery Current High

Setting for the battery amps alarm. When the total current to the battery

exceeds this setting, the alarm is activated and the message

BATTERY

CURRENT HIGH

is displayed on the GUI.

Load Current High

Setting for the load amps alarm. When the current to the load has exceeded

this setting, an alarm is activated and the message

LOAD CURRENT HIGH

is

displayed on the GUI

6.6.5.2 Voltage Alarms

AC Mains High

Activates an alarm when the AC exceeds the specified setting. The message

AC MAINS HIGH

displays on the GUI.

AC Mains Low

Activates an alarm when the AC input to the power system falls below the

specified setting. The message

AC MAINS LOW

displays on the GUI.

High Voltage [1-2]

Activates an alarm when the power system DC voltage exceeds the specified

value. The message

HIGH VOLTAGE 1 (or 2)

displays on the GUI.

Low Voltage [1-2]

Activates an alarm when the power system DC voltage falls below the

specified value. The message

LOW VOLTAGE 1 (or 2)

displays on the GUI.

Midpoint Monitor [1-5]

Activates an alarm when the voltage reading (1 through 5) exceeds the

specified setting (from the midpoint). The message

MIDPOINT MONITOR 1

(or

2-5) displays on the GUI.

6.6.5.3 Battery Alarms

Battery Runtime Low

Allows specification in hours when the battery runtime alarm will activate with

respect to the hours remaining in the battery runtime prediction.

Battery Capacity
(Remaining) Low

Allows specification of the battery capacity alarm trigger point as a

percentage. When the capacity of the battery is depleted to this specified

value, the capacity alarm is activated.

Battery Overtemp

Activates an alarm when the specified temperature is reached.

Battery On Discharge

Activates an alarm when the battery is on discharge; e.g., during AC Fail or

BT mode.

Battery Test

Activates an alarm when the Battery Test is in progress.

Boost Mode

Activates an alarm when BST mode is activated.

6.6.5.4 Temperature Alarms

Temp Sensor Fail [1-4]

Activates an alarm when any temperature sensor fails

TC Sensor Fail

Activates an alarm when a sensor, enabled for Temp Comp, fails