Features, System overview, Tiered distribution features – Alpha Technologies CXPS 48-2T 48V Pos Gnd User Manual

Page 13: Overview (vista ii two-tier), Eatures, 2 features

Advertising
background image

Argus Technologies Ltd.

053-393-C0 Rev A WC

Printed in Canada. © 2007 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 3 of 32

2 Features

2.1 System

Overview

The basic system configuration is called out by Argus part number 053-393-20-000 (Figure 1); which includes:

• 1200A Two-Tier Distribution Center (Vista II Two-Tier UDC)

• Cordex System Modular Controller 4RU (CXCM4)

• Two (2) Cordex 48-3.6kW 6-module rectifier shelves

• Kydex rear cover

• 23” rack mount rails

• System integration cabling and bus work.

Optional system configurations are available as:

053-393-20-010: basic configuration factory installed into a 22RU battery mount 23” relay rack.
053-393-20-020: basic configuration factory installed into a 7 foot 23” zone 4 relay rack.
053-393-20-030: basic configuration factory installed into a 7 foot 23” zone 4 relay rack and three (3) battery

trays with cabling and 100A battery disconnects for up to three (3) 48V VRLA strings.

2.2 Tiered

Distribution Features

2.2.1

Overview (Vista II Two-Tier)

The 1200A Two Tier Distribution Center is a modular, front access system that provides DC distribution, rectifier
and battery connections. Coupled with Argus Cordex system controller, rectifiers and converters, it provides a
complete solution in a compact integrated package.

The distribution center in the CXPS 48-2T is configured at the factory with:

• 48V, 20-position breaker tier with 600A low voltage disconnect (LVD)

• 48V, 18-position split-breaker tier with 600A LVD (can also be configured for split 48V/24V voltage

applications)

• 48V, 10-position, 30A GMT fuse assembly

• Load shunts for current measurement.

The modular distribution center allows customization of integrated power systems; perfect for space-restricted
installs. The system provides front access to controller interface and I/O connections, load breakers & fuses, and
battery connections.

Figure 2–Example of distribution center in the CXPS 48-2T