Converter output cabling (+24v hot connection) – Alpha Technologies CXPS 48-2T 48V Pos Gnd User Manual

Page 31

Advertising
background image

Argus Technologies Ltd.

053-393-C0 Rev A WC

Printed in Canada. © 2007 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 21 of 32

Figure 11–Rear of CXPS 48-2T system showing converter -GND output connection

and converter +24V wire routing location

Converter Output Cabling (+24V HOT Connection)
Terminate the #2 AWG cable with pre-terminated 1/4”-5/8”C lug (With wire marker #16) to the
+24V (hot) output terminal labeled “E3” using hardware supplied with shelf.

Route the un-terminated wire end up in between the system bus bars towards the front of the
distribution center (reference Figure 11 for routing location).

Fish the wire through the existing hole in the glastic insulator of the bottom distribution tier
(reference Figure 12 for routing location).

Cut wire to size, strip cable sheath, and crimp supplied 3/8”-1”C lug. Note: This lug must be
crimped after it has been routed through the distribution tier.

Attach lug to input bar using the hardware originally used for attaching copper jumper bar.

Converter output (+24V)
wire routing location

Converter output (-GND)
wire connection location