Page 19 of 32

proper cable management and to not overload the capacity of a single tier (600A LVD
limitation).

TPS fuses may be used instead of breakers via a plug-in breaker cartridge, which installs into
any AM-type plug-in breaker panel configuration. See Figure 9 below:

Figure 9–Plug-in breaker/fuse cartridge

5.4.2.2 GMT

Fuses

The CXPS 48-2T is factory configured with (10) GMT type fuse positions for additional 48V load
distribution. The fuse assembly is rated for maximum capacity of 30A.

Connections for hot and return are made via screw terminal connections on the assembly.

Figure 10–GMT fuses

5.5

DC-DC Converter Connections

The CXPS 48-2T is factory configured as a 48Vdc power system. A dual 48/24V output option is available via
factory or field upgrade with DC-DC converters.

Reference the DC-DC converter manual for full installation and operation procedures.