Specifications for Argus’ CXPS 48-2T 48Vdc Power System

Argus Technologies Ltd.

053-393-B1 Rev A WC

Printed in Canada. © 2007 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 1 of 3

Output

Voltage:

42 to 60Vdc within rated limits


Current:

System: up to 825A standard configuration,
(expandable to 1200A via additional rectifier shelf)
Rectifier: 67A @ 48Vdc nominal (75A max.)


Power:

System: up to 39,600W standard configuration,
(expandable to 57,600W via additional rectifier shelf)
Rectifier: 3600W maximum


Heat Dissipation (per rectifier): <1415 BTU per hour

Static Load Regulation:

Better than ±0.1% for any load change within rated limits


Dynamic Load Regulation:

Better than ±2% for 40% - 90% load step
(output shall recover to static limits within 30ms)


Static Line Regulation:

Better than ±0.1% for any change in input voltage within rated limits


Electrical Noise:

<32dBrnC (voice band)
<20mVrms 10kHz to 10MHz (wideband)
<100mVp-p 10kHz to 100MHz
<1.0mV (psophometric)


Acoustic Noise:

<60dBa @ 1m (3ft.) @ 30°C (86°F)


Input

Voltage:

208, 220, 230, 240, 277Vac nominal


Operational Range:

176 to 320Vac


Extended Operation:

Low: 176 to 90Vac (derated power)


Frequency:

45 to 66Hz


Current:

16.8A @ 240Vac
19.4A @ 208Vac
22.8A @ 176Vac (maximum)


Recommended Feeder Breaker
Single Phase:

30A, #10 AWG (for a single rectifier module)

Three Phase:

50A, #6 AWG delta connection (for three rectifier modules)
30A, #10 AWG wye connection (for three rectifier modules)


Power Factor:

>0.99 at nominal conditions and 50-100% load


Protection:

10kA-interrupting capacity fuses in active and neutral lines


Efficiency:

>90% at nominal conditions and 50-100% load