Specifications for Argus Technologies’ CXPS 48-2T 48Vdc Power System Continued

Argus Technologies Ltd.

053-393-B1 Rev A WC

Printed in Canada. © 2007 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 2 of 3

Connections

Load Connections:

AM breakers (1-pole): 1/4” holes on 5/8” centers
AM breakers (multiple pole): 3/8” holes on 1” centers
GMT fuses: screw terminals 0.34mm

2

to 4mm

2

(#22 to #12 AWG)


Battery Terminations:

3/8” holes on 1” centers, 4 sets per polarity


Rectifier Terminations:

3/8” holes on 1” centers


Alarm Connections:

0.081mm

2

to 4mm

2

(#28 to #12 AWG)


Cable Access:

Top and/or bottom


Environmental

Operating Temperature:

-40 to +75°C, power derated above 65°C (149°F)
(-40 to 167°F)


Storage Temperature:

-40 to +85°C
(-40 to 185°F)


Humidity:

0 to 95% non-condensing


Elevation:

-500m to 2800m; to 4000m with temperature derated to 40°C
(-1640 feet to 9186 feet; to 13124 feet with temperature derated to 104°F)


Miscellaneous

Maximum Number of Rectifiers: Up to eleven (11) Cordex 48-3.6kW modules

#010-600-20 (pre-RoHS #010-567-20);
NOTES: One rectifier space is occupied by the CXCM4
#018-586-20 (pre-RoHS #018-574-20)


Distribution Capacity:

Tier 1: Up to eighteen (18) 48V, AM plug-in style breakers, 600A maximum
NOTE: Tier may be factory or field configured for eight (8) 48V breaker positions
and ten (10) 24V breaker positions for an optional 48V-24V DC-DC converter
installation

Tier 2: Up to twenty (20) 48V, AM plug-in style breakers, 600A maximum

Up to ten (10) 48V, GMT fuse positions
NOTE: Maximum 30A per GMT fuse assembly


Dimensions:

584mm W x 755mm H x 477mm D
(23” W x 29.7” H x 18.8” D)
[for additional options see outline drawings at the rear of this manual]


MTBF (rectifier module):

>350,000 hours ground benign @ 30°C (86°F)