2.3.4 Analog Inputs

Temperature inputs

Two temperature input channels, T1 and T2, provide monitoring of battery or room/ambient temperature. Voltage

is supplied to these terminals to power the temperature sensors.

Voltage inputs

Two voltage input channels, V1 and V2, are used to monitor the system voltage. The controller software is pre-

configured to monitor V1 for load voltage A and V2 for load voltage B.

Current inputs

The controller software is pre-configured to monitor I1 for load current A and I2 for load current B. It is wired inter-

nally to the system current shunt.

2.3.5 Digital Input Channels

The CXCP can accommodate up to eight digital input channels. Each channel responds to a zero or system volt-

age potential at the input to activate or deactivate the appropriate condition.
Some of these channels are pre-assigned to monitor specific signals. See the software manual for more informa-

tion. Refer also to the electrical schematic that ships with your system.

2.3.6 Alarm and Control Output Relays

Each CXCP contains eight standard and eight optional Form C alarm output relays to extend alarms and control

to external apparatus. Each internally generated alarm or control signal can be mapped to any one of the 16

relays, or, several signals may be mapped to just one relay or none at all.

Relays

Digital Inputs

Figure 8 — Controller I/O and alarm interface