2.2.1 Distribution Shunts
Each bank of breakers can be connected to the distribution bus via an optional 800 A / 25 mV shunt and the
individual distribution shunt current can be viewed on the CXC. Refer to the electrical schematic that ships with
your system.
Figure 3 — Breaker bank shunt (left shunt shown in a dual feed BDFB)
2.2.2 Shunt Multiplexer Panel
The Cordex controller can monitor up to four current input channels, such as load currents and battery charge
currents. When the number of current inputs is more than four, an optional shunt multiplexer panel monitors the in-
dividual branch load currents within the BDFBs and sends the current measurements to the CXC for data logging
and display.
Figure 4 — Shunt mux panel mounted on the inside door of the top BDFB