Hardware Specifications, CXCM2

CPU: Coldfire

RAM: 8MB

Flash:

4MB standard, 8MB optional


Display:

160 x 160 pixel grayscale LCD


Front Panel Controls:

Reset button and touch panel (display and input device)


LED’s:

System OK (Green)
Power System Minor Alarm (Yellow)
Power System Major Alarm / Controller Fail (Red)


Audio:

Built-in speaker for alarm and popup message tones


Dimensions:

86mm H x 128mm W x 255mm D
(3.4” H x 5.0” W x 10“ D)


Weight:

1.8 kg (3.9 lb.)


Mounting:

Integrated on Cordex 2RU series 19” and 23” shelves


Communication Ports:

Ethernet RJ-45, CAN [see shelf specifications]


Relay Outputs:

Six (6) Form C, 60Vdc 1A maximum


Digital Inputs:

Six (6), 0 to 60Vdc


Analog Inputs and System Signals, Argus #018-573-20-040:

Two (2) DC voltage, 0 to 60Vdc
One (1) current, ±50mV
Two (2) temperature, 0 to 20Vdc with power source


Analog Inputs and System Signals, Argus #018-573-20-044:

Two (2) DC voltage, 0 to 60Vdc
Two (2) current, ±50mV
Two (2) temperature, 0 to 20Vdc with power source
Four (4) bi-voltage, ±60Vdc


Recommended Signal Wire Sizes (as per UL/CSA)

Wire Size Range*:

0.14 to 0.75mm

2

(#26 to #18 AWG)
via DB connectors or terminal block kit (see list options)


Temperature Range:

0 to 50°C
(32 to 122°F)


CAUTION – TO REDUCE RISK OF FIRE, USE ONLY 0.14mm

2

(#26 AWG) OR LARGER WIRE.


* See drawings at the rear of this manual.

The above information is valid at the time of publication. Consult factory for up-to-date ordering information. Specifications are subject to change without notice.