Connections, Environmental, Miscellaneous – Alpha Technologies CXPS 48-1.8-M2, 48V Pos Gnd User Manual

Page 6

Advertising
background image

Specifications for Argus Technologies’ CXPS 48-1.8-M2 48Vdc Power System Continued

Argus Technologies Ltd.

053-991-B1 Rev A WC

Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 2 of 3

Connections

Load Connections:

AM breakers (1-pole): 1/4” holes on 5/8” centers
AM breakers (multiple pole): 3/8” holes on 1” centers (with adapter)

Battery Terminations:

AM breakers (1-pole): 1/4” holes on 5/8” centers
AM breakers (multiple pole): 3/8” holes on 1” centers (with adapter)


Alarm/Signal Connections:

0.14mm

2

to 1.50mm

2

(#26 to #16 AWG)


AC Input:

Terminal blocks 2.5mm

2

to 6mm

2

(#14 to #10 AWG),

individual feeds for each module


Cable Access:

Front and top


Environmental

Operating Temperature:

-40 to +65°C, power derated to 75°C (167°F)
(-40 to 149°F)


Storage Temperature:

-40 to +85°C
(-40 to 185°F)


Humidity:

0 to 95% non-condensing


Elevation:

-500m to 2800m; to 4000m with temperature derated to 40°C
(-1640 feet to 9186 feet; to 13124 feet with temperature derated to 104°F)


Miscellaneous

Number of Rectifiers:

Up to seven (7) Cordex 48-1.8kW modules;
Argus #010-602-20 (pre-RoHS #010-580-20)


Distribution Capacity:

Load:

14x 1-pole positions, plug-in type (bullet terminals), AM-style, 5 to 250A

Battery:

4x 1-pole positions, plug-in type (bullet terminals), AM-style, 5 to 250A


Dimensions:

438mm W x 311mm H x 310mm D
(17.24” W x 12.25” H x 12.2” D)
[-000 configuration – excludes mounting brackets, rear cover, and module
handles. For additional options see outline drawings at the rear of this manual.]


MTBF (rectifier module):

>400,000 hours ground benign @ 30°C (86°F)


Advertising