Distribution cabling, Breaker output (hot) connections, Breaker return (ground) connections – Alpha Technologies CXPS 48-1.8-M2, 48V Pos Gnd User Manual

Page 32: Battery breaker connections, Figure 9–rear view of dcp03 distribution panel

Advertising
background image

Argus Technologies Ltd.

053-991-C0 Rev A WC

Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 18 of 28

DCP03 input bar (hot)

DCP03 input bar (return)

Figure 9–Rear view of DCP03 distribution panel

5.6.2 Distribution

Cabling

Refer to guidelines supplied with the load equipment. Typically distribution cables are sized to provide a 0.5V loop
drop at full load as well as meeting ampacity requirements of the protection fuse or circuit breaker.

Distribution cabling must be terminated with 1/4”–5/8”C lugs for connecting to DCP03.

5.6.3

Breaker Output (Hot) Connections

Connect breaker (hot) output connections before connecting the breaker returns. Secure two hole lugs to the 1/4”
studs (on 5/8” centers) using the supplied hardware with the DCP03. Cables should run directly out the rear of the
distribution center. Refer to Figure 10.

5.6.4

Breaker Return (Ground) Connections

Connect breaker (ground) output connections to the DCP03 ground bar. Secure two hole lugs to the 1/4” holes
(on 5/8” centers) using the supplied hardware with the DCP03. Cables should run directly out the rear of the
distribution center above the breaker (hot) output cables. Refer to Figure 10.

5.6.5

Battery Breaker Connections

Connect battery breaker (hot) connections first using the same guidelines as the load cable installation. Connect
battery ground connections using the same guidelines as load returns. Cables should run directly out the rear of
the distribution center above the breaker (hot) output cables. Refer to Figure 10.

Figure 10–Battery, load, and return connection locations

Battery (hot) connection

Load breaker (hot) connection

System return (ground) bar