7.2.1

Output Voltage Modes

Voltage modes can be thought of as modes that, under software control, can directly adjust the output voltage.
The qualification of ‘under software control’ is made because there are processes that occur in the rectifier that
can change the output voltage that do not adjust the output voltage directly (such as the rectifier being in current
limit).

The following table lists the four Output Voltage Modes and a description of when they are active:

Output Voltage Modes

Active when…

Float

Output voltage is set to the float voltage setting.

Equalize

Output voltage is set to the equalize voltage setting.

Battery Test

Output voltage is set to the battery test voltage setting.

Safe

Output voltage is set to the safe mode voltage setting.

Table D–Output voltage modes

7.2.2

Output Current/Power Modes

These modes directly affect the output current and power.

The following table lists the four Output Current/Power Modes and a description of when they are active:

Output Current/Power Mode

Active when…

Temperature foldback mode

Output current and power limit have been reduced due to high temperature of the
heatsink or internal ambient temperature sensor.

AC foldback mode

Output current and power limit have been reduced due to low AC input voltage. Note:
this will reduce the risk of tripping an AC breaker due to increased AC current draw as
the AC voltage decreases.

Short circuit foldback mode

Output current limit has been reduced due to a short circuit at the output.

Internal fault foldback mode

Output current limit has been reduced due to an internal fault.

Table E–Output current/power modes

7.3

Factory Ranges and Defaults

The following table lists the rectifier settings/ranges/defaults; changes are made via the CXCM2:

Setting

Range (minimum to maximum)

Default

Float (FL) Voltage

47.5 – 58.2V

54V

Equalize (EQ) Voltage

49.8 – 60.2V

55V

Battery Test (BT) Voltage

44 – 52V

46V

Safe Mode Voltage

46 – 56V

51.4V

OVP

See note below – 63V

57V

Current Limit (CL)

20 – 100%

100%

Power Limit (PL)

0 – 100%

100%

Module Start Delay

0 – 250s

1s

System Start Delay

0 – 600s

0s

Low Voltage Alarm (LVA)

42 – 52V

44V

High Voltage Alarm (HVA)

52 – 63V

55.5V

EQ Timeout

1 – 2399h

30h

BT Timeout

1 – 250h

8h

Softstart Ramp-rate

Normal/Fast Normal

CL/PL Alarm

Enable/Disable

Enable

Remote Shutdown

Enable/Disable

Enable

Ramp Test

Enable/Disable

Enable

Table F–Cordex 48-1.8kW factory ranges and defaults

NOTE:

OVP cannot be set below the present system/FL/EQ/BT voltage setting or the safe mode voltage (default) of 51.4V.