2.3.3 LED

lights

Three LED lights are located on the front panel, one green, one yellow, and one red. The lights are used to
display the alarm status of the power system, controller progress and status during startup, and file transfers.

2.3.3.1 Alarm

conditions

Only one LED light is illuminated at a time during alarm conditions. Each LED light corresponds to a specific
alarm.

Illuminated

LED light

Alarm

Green

OK, no alarms

Yellow

Minor alarm, no major alarms

Red Major

alarm

2.3.3.2 Progress

and

status

indication

The LED lights are also used in the following situations:

Illuminated

LED light

Situation

All three

Base unit validation

Red File

transfer

2.3.4 Reset

button

A reset button is located on the front panel for restarting the controller’s microprocessor. Select the reset menu
item before pressing the reset button. Refer to the software manual.

2.3.5 Modem

port

A modem port is located on the front panel. It is designed to be used in conjunction with an Alpha DB-9 connector
and an Alpha Cordex DC Modem #018-585-20.

CAUTION: Connect the modem port with an Alpha-supplied modem and cable only. Otherwise,
equipment damage may result.

2.3.6 Ethernet

port

An Ethernet port is located on the front panel. This port is designed to connect the controller to a user supplied
TCP/IP network. Use a standard RJ-45 jack with a standard network cable.

The Ethernet port can be used for local access, for example to a laptop computer. Use a standard network
crossover cable for the connection.

2.3.7

Analog input channels

The controller is supplied with analog input channels for voltage, current, and temperature.

2.3.7.1 Voltage

inputs

Two voltage input channels, V1 and V2, are used to monitor the discharge and charge voltage. The controller
software is pre-configured to monitor V1 for load voltage and V2 for battery voltage. V2, which is wired internally,
is used as a system reference for the rectifier float voltage, low voltage disconnect (LVD), system high voltage
alarm, and system low voltage alarm.

2.3.7.2 Current

inputs

The controller software is pre-configured to monitor I1 for load current. It is wired internally to the system current
shunt.