Alpha Technologies CXPS-HD 48-1.2-225 User Manual

Page 40

Advertising
background image

Specifications for Alpha CXPS-HD 48-1.2-100 and CXPS-HD 48-1.2-225 48Vdc
Power Systems

Alpha Technologies Ltd.

0530082-S0 Rev B

Printed in Canada. © 2011 Alpha Technologies Ltd. ALPHA and CORDEX are trademarks of Alpha Technologies Ltd. All Rights Reserved.

Page 1 of 4

Output

Voltage 48

Vdc

(nominal)


Current

System model CXPS-HD 48-1.2-100:

100 A max @ 48 Vdc (nominal input)

50 A max @ 48 Vdc (115 Vac input)

System model CXPS-HD 48-1.2-225:

225 A max @ 48 Vdc (nominal input)

112.5 A max @ 48 Vdc (115 Vac input)


Rectifier

Module:

25 A max @ 48 Vdc (nominal input)

12.5 A max @ 48 Vdc (115 Vac input)

(subject to de-rating below 110 Vac input)


Power

System model CXPS-HD 48-1.2-100:

4800 W max @ 48 Vdc (nominal input)

2400 W max @ 48 Vdc (115 Vac input)


System model CXPS-HD 48-1.2-225:

10800 W max @ 48 Vdc (nominal input)

5400 W max @ 48 Vdc (115 Vac input)


Rectifier

Module:

1200 W max @ 48 Vdc (nominal input)

600 W max @ 48 Vdc (115 Vac input)


Heat Dissipation

< 308 BTU per hour per rectifier module


Static Load Regulation

Better than ±0.5% for any load change within rated limits


Dynamic Load Regulation

Better than ±2% for 10% to 90% load step

(output shall recover to static limits within 10 ms)


Static Line Regulation

Better than ±0.1% for any change in input voltage within rated limits


Dynamic Line Regulation

Better than ±1% for any change in input voltage within rated limits

(output voltage should recover to static limits within 2 ms)


Electrical Noise

< 38 dBrnC (voice band)
< 30 mVrms 10 kHz to 10 MHz (wideband)
< 150 mVp-p 10 kHz to 100 MHz
< 2.0 mV (psophometric)


Acoustic Noise

< 60 dBa @ 1 m (3 ft.) @ 30°C (86°F)

Advertising