7 operation – Alpha Technologies CXPS-HD 48-1.2-225 User Manual

Page 33

Advertising
background image

0530082-J0 Rev B

Page 25 of 31

7 Operation

7.1

Main rectifier states

Rectifier operation can be broken up into five main states:

1. Off
2. Start

Delay

3. Soft

Start

4. Normal

Operation

5. Turning

Off

Each state is distinct and necessary for the operation of the rectifier. These states are briefly described below.

7.1.1 Off

state

The rectifier is in the Off state immediately after power is applied to the rectifier or after a rectifier shutdown. The
shutdown source could be a remote or local shutdown, an AC shutdown, an over voltage shutdown, or a thermal
shutdown.

When the rectifier is in the Off state, the DC-DC converter is turned off. The controller monitors its inputs for the
proper conditions that allow the start-up sequence.

When the rectifier start-up conditions have been met, the rectifier transitions to the Start Delay state.

7.1.2

Start Delay state

When the rectifier is in the Start Delay state, the DC-DC converter is held off and not sourcing power, and waits
for a predetermined time before transitioning to the next state.

The controller continues to monitor its inputs during the Start Delay state.

After the Start Delay state, the rectifier transitions to the Soft Start state.

7.1.3 Soft

Start

state

When the rectifier is in the Soft Start state, the voltage and current output of the rectifier are gradually increased.
This gradual increase reduces the instantaneous load on the AC source. If a load is present, the rectifier begins to
source power.

When the voltage and current limits are reached, the rectifier transitions to the Normal Operation state.

7.1.4 Normal

Operation

state

During the Normal Operation state, the rectifier is performing all of its specified rectifier functions.

From this state, the only valid transition is to the Turning Off state, which happens if the rectifier is required to shut
down.

7.1.5 Turning

Off

state

The Turning Off state consists of a short delay required to initialize some parameters before the rectifier actually
shuts off.

After the short delay, the rectifier transitions to the Off state.