3.5 Battery Refurbishment Plan

Does battery meet

the minimum

conductance values

per Table 1?

Yes

Measure

Conductance

Measure

Battery

Voltage

Sort Batteries per

Conductance &

Voltage

Batteries Returned

from Site. Measure

and document 24

hour Open Circuit

Voltage (OCV).

(

Must occur within 24

hours of removal from

charger)

Properly recycle

batteries per EPA

requirements

Battery

Refurbishment

Plan

Group re-deployable

batteries as indicated for

future deployment as

strings

No

Yes

Does battery meet

the minimum of

12.6 Volts for the 24

hour OCV?

Measure

Battery

Voltage

Batteries stored in

warehouses for

extended periods of

time refer to “Important

Storage Practices” on

page 8.

No

Fig. 7, Flow Chart for Battery Refurbishment Plan