Electrical safety, Important storage practices – Alpha Technologies AlphaCell HP User Manual

Page 8

Advertising
background image

745-680-C5-002, Rev. A

8

Fig. 1, Capacity vs. Storage Time

During storage please note:
• All lead acid batteries experience self-discharge while in open circuit storage. This causes circuit

voltage and capacity to decrease.

• The self-discharge rate is related to ambient temperature. The lower the temperature, the less

the discharge. Batteries should be stored in a clean, ventilated, and dry location with an ambient

temperature of 32ºF to 77ºF (0ºC to 25ºC).

• It is important to track open circuit voltage which is related to the density of the electrolyte. If

the open circuit voltage is lower than 12.6V or the batteries have been stored beyond the limits

shown in Figure 1, the batteries should be charged to avoid damage caused by self-discharge.

• All batteries should be fully charged before storage. Record the storage date and next

supplemental charge date in a maintenance record and on the battery.

• Upon battery deployment, verify all batteries within each string measure in the range of

+/- 0.3Vdc of the string average.

Electrical Safety

• Lethal voltages are present within the power supply and electrical enclosures. Never assume that

an electrical connection or conductor is not energized. Check circuits with a volt meter prior to any

installation or removal procedure.

• Observe circuit polarities.
• Always use the buddy system when working under hazardous conditions.
• Ensure no liquids or wet clothes contact internal components.
• Hazardous electrically live parts inside this unit are energized from batteries even when the AC input

power is disconnected.

• Use an insulated blanket to cover exposed portions of the battery system when performing extended

maintenance that could result in personal or equipment contact with the energized conductors.

• Certain types of rectifier circuits used in charging the battery may not include a line isolating transformer.

In these cases extreme caution should be used when maintaining and collecting data on the battery

system.

The product warranty is void if the batteries are not stored and recharged in accordance with these guidelines.

NOTE:

Important Storage Practices

0

3

6

9

12

15

18

21

24

2.1

2.13

2.16

2.15

2.17

2.14

2.12

2.11

80%

95%

90%

100%

85%

75%

70%

Percent State of Charge

OCV Per Cell

Storage Time (Months)

77°F/

25°C

68°F/

20°C

86°F/

30°C

104°F/

40°C