0 troubleshooting, continued – Alpha Technologies AlphaCell HP User Manual

Page 25

Advertising
background image

25

745-680-C5-002, Rev. A

5.0

Troubleshooting, continued

Problem with

Symptom

Possible Causes

Possible Result

Corrective Actions

DC Voltage

Checks

System float voltage >

2.3V/C average 77°F

(25°C)

Charger output set

incorrectly

Overcharging causes

excessive gassing and

drying out of electrolyte

and contributes to potential

thermal runaway.

Reset the charger output

voltage to recommended

value.

System float voltage <

2.25V/C average 77°F

(25°C)

Charger output set

incorrectly

Undercharging results in

gradual loss of operating

time and capacity with

successive discharge cycles.

If persistant, an irreversible

level of lead sulfate develops

on the plates resulting in a

permanent capacity loss

Reset the charger

output voltage to

recommended value.

Equalize battery system

from 48 to 72 hours

and perform capacity

test. If capacity loss is

permanent, replace the

total battery system.

Individual battery float

voltage > 13.3 Vdc

Potentially the

individual battery has

shorted cell

Verify with impedance

or conductance check

Reduced operating time

under load. Increased float

current. Heating of cell during

discharge. Contributes to

potential thermal runaway.

Replace individual battery.

Individual battery float

voltage 14.5 Vdc for

6 cell

Potentially open cells in

individual battery. Confirm

by checking for zero float

current or check for very

high impedance of the

battery.

Failure to support load. Could

result in an internal arc, could

ignite gasses within the cell.

Replace individual battery.

DC voltage measured

between battery system

output terminals and

ground (rack) or a

ground fault indicated

by automatic monitoring

equipment.

Damaged container allow-

ing electrolyte to wick out

to grounded surface (rack).

Personnel shock hazard

resulting in serious

injury or electrocution.

Potential burning of

container at damaged

area or battery fire.

Determine the source of

ground fault and replace

battery.

Temperature

Checks

Elevated room tem-

perature

Lack of adequate air condi-

tioning or ventilation

Reduced battery life

Cool room or accept reduced

battery life

Elevated battery temp.

Elevated room temp.

Inadequate cabinet

ventilation

Discharge - charge

cycle

Reduced battery life

Reduced life and

potential thermal

runaway

Normal if not exceeding

18°F increase

Improve room air

conditioning

Improve cabinet

ventilation

Limit recharge current

High current recharge

High charging voltage

Shorted cells

Normal if not exceeding

18F/10C increase over

ambient

Limit recharge current

Reduce within

specifications

Replace shorted cells

and evaluate total string.

Table 2, Troubleshooting, continued

Advertising