Chemical hazards, Mechanical safety – Alpha Technologies AlphaCell HP User Manual

Page 9

Advertising
background image

9

745-680-C5-002, Rev. A

Chemical Hazards

Any liquid emissions from a valve-regulated lead-acid (VRLA) battery contains dilute sulfuric acid, which is

harmful to the skin and eyes. Emissions are electrolytic and are electrically conductive and corrosive.
To avoid injury:
• Servicing and connection of batteries shall be performed by, or under the direct supervision of, personnel

knowledgeable of batteries and the required safety precautions.

• Always wear eye protection, rubber gloves, and a protective vest when working near batteries. To avoid

battery contact, remove all metallic objects, (such as rings or watches), from your person.

• Batteries produce explosive gases. Keep all open flames and sparks away from batteries.
• Use tools with insulated handles, do not rest any tools on top of batteries.
• Batteries contain or emit chemicals known to the State of California to cause cancer and birth defects

or other reproductive harm. Battery post terminals and related accessories contain lead and lead

compounds. Wash hands after handling (California Proposition 65).

• If any battery emission contacts the skin, wash immediately and thoroughly with water. Follow your

company’s approved chemical exposure procedures.

• Neutralize any spilled battery emission with the special solution contained in an approved spill kit or with

a solution of one pound (454g) bicarbonate of soda to one gallon (3.8l) of water. Report a chemical spill

using your company’s spill reporting structure and seek medical attention if necessary.

• Always replace batteries with those of an identical type and rating

(match conductance, voltages, and

date codes as specified in this document).

• Never install old or untested batteries.
• Prior to handling the batteries, touch a grounded metal object to dissipate any static charge that may have

developed on your body.

• Use special caution when connecting or adjusting battery cabling. An improperly or unconnected battery

cable can make contact with an unintended surface that can result in arcing, fire, or a possible explosion.

• A battery showing signs of cracking, leaking, or swelling should be replaced immediately by authorized

personnel using a battery of identical type and rating.

Mechanical Safety

• Keep hands and tools clear of fans.
• Fans are thermostatically controlled and will turn on automatically.
• Power supplies can reach extreme temperatures under load.
• Use caution around sheet metal components, especially sharp edges.
• Depending on the model, batteries can weigh anywhere from 25 to 100 pounds (11kg to 45kg). Exercise

care when handling and moving batteries. Use proper handling equipment.

WARNING!