2.9 Output, Alarm and Oil LEDs

Before connecting or reconnecting a power supply to the generator, check that it is in good condition and that its

electrical rating does not exceed that of the generator.

CAUTION!

Use Fig. 2-10 and Table 2-1 to understand the different LED states of the generator.

Fig. 2-10, Control Panel

(data values shown for illustration purposes only)

OUTPUT BREAKER

LCD Display

V: 40.3V I: 00.0A

P:0000W

Oil: OK ALM:
Time: 004H 27M

Ground Stud

DC OUTPUT

OUTPUT

ALARM

OIL

ENGINE

ON

OFF

State

LED State

LCD Display Text

Output State

Corrective Action

Normal Operation

V = Voltage (V)

I = Current (A)

P = Power (W)

Oil = “_OK”

ALM = no display

Time = Hour; Min

Engine running; Output

ON

Overload

ALM = “OL”

Engine running; Output

OFF after 2-3 seconds

Disconnect the power supply

and investigate the cause of the

overload; manual reset (the output

LED should turn green within 10

seconds)

Module Overheat

ALM = “OH”

Engine running; Output

OFF after 5 seconds

Manual reset

Critical Low Oil

Shutdown

Oil = “LO_”

(Display stays on

2-3 seconds after

alarm initiates)

Engine OFF; Output

OFF

Replenish oil; manual reset

Table 2-1, LED States

OUTPUT

ALARM

OIL

ALARM

(if possible)

(stays on 2-3

seconds after

alarm initiates)

(flashes during

overload)