2.1 Oil Level

Power OFF the generator engine and place on a level surface before servicing.

WARNING! ELECTRICAL HAZARD

• Using non-detergent oil or 2-stroke engine oil will shorten service life and void the warranty. Use only

high-detergent, premium quality, 4-stroke engine oil, certified to meet U.S. automobile manufacturer’s

requirements for API Service Classification SG/SF/SJ/SL/SM/SN. Use synthetic SAE 10W-40

viscosity oil unless operating at ambient temperatures below 32°F (0°C). For temperatures below

32°F, use synthetic SAE 0W-40 viscosity oil.

• Change the oil in a new engine within 4-6 hours of operation to clean any contamination or

manufacturing debris.

• Running the engine with low oil can cause serious damage.

• The Low Oil Alarm System will automatically stop the engine before the oil level falls below a safe

limit. To avoid an unexpected shutdown, inspect the oil level regularly.

CAUTION!

Tools Required:

#2 Philips Head Screwdriver

Oil Drain Pipe
Procedure:
1. Remove the maintenance cover.
2. Using the slots in the oil drain pipe, remove the dipstick, wipe with a clean rag and reinsert, screw

down until tight.

3. Remove the dipstick to check the oil level.
4. If the oil level is below the lower level of the dipstick, refill to the top of the upper level marking. Do not

overfill.

5. Reinsert the dipstick and screw down until tight.

2.0 Operation

Fig. 2-1, Checking Oil Level

L

L/2

Dipstick

Oil Fill Hole

Minimum

Oil Level

Maximum

Oil Level