2.0

Installation, continued

2.5

Connecting the Utility Power, continued

2.5.2 Wiring From Duplex Receptacle to Service Disconnect

In most cases, the following configurations (see next page) qualify for service entrance
use, however, other codes may apply. Always contact your local utility to verify that
the wiring conforms to applicable codes.

240VAC Service (XM Series 2 915-240 Power Supply) Enclosures used with the XM
Series 2 915-240 are equipped with a 240VAC duplex receptacle to provide power to
the power supply and peripheral equipment. The receptacle, NEMA 6-15R, is protected
by a single, 2-pole, common trip 15 Amp circuit breaker located inside the service
entrance. Wiring is typically 14AWG per NEC code, a grounding clamp, located on the
enclosure, facilitates dedicated grounding.

120VAC 20A Service (XM Series 2 915-120 Power Supply):

Enclosures used with the XM Series 2 915-120 are equipped with a 120VAC duplex
receptacle to provide power to the power supply and peripheral equipment. The recep-
tacle, NEMA 5-20R, is protected by a single, 1-pole, 20 Amp circuit breaker located
inside the service entrance. Wiring is typically 12AWG per NEC code, a grounding
clamp, located on the enclosure, facilitates dedicated grounding.

120VAC 15A Service (XM Series 2 615 Power Supply):

Enclosures used with the XM Series 2 615 are equipped with a 120VAC duplex
receptacle to provide power to the power supply and peripheral equipment. The recep-
tacle, NEMA 5-15R, is protected by a single-pole, 15 Amp High Magnetic circuit
breaker located inside the service entrance. Wiring is typically 14AWG per NEC code,
a grounding clamp, located on the enclosure, facilitates dedicated grounding.

Alpha recommends wiring with 12AWG, in the event that the enclosure will be upgraded to use 90V power
supplies.

to utility

neutral (white)

neutral bus

Copper ground wire

#8 AWG (minimum)

L1 (black)

breaker

grounding point made

to enclosure wall

L1 (black)

120VAC Service Entrance Wiring

to enclosure
receptacle

Typical 240VAC Service Entrance Wiring

to utility

neutral (white)

neutral bus

Grounding point

made to enclosure

wall

L2

L1

breaker

Copper ground wire

#8AWG (minimum)

L2 (red)

L1 (black)

to enclosure
receptacle

Fig. 2-8, Typical Service Entrance Wiring

When required to bond the box to the neutral plate, use the long green bonding screw provided with the box:
Alpha P/N 523-011-10 or Square D P/N 40283-371-50.