Klp/klr programming characteristics - local, Klp/klr programming characteristics - digital, Klp/klr programming characteristics - analog – Atec Kepco-KLP Series User Manual

Page 5

Advertising
background image

KLP/KLR PROGRAMMING CHARACTERISTICS - LOCAL

SPECIFICATION

RATING/DESCRIPTION

CONDITION

Local Control

Rotary encoders

Panel mounted

Local Control

Coarse

~100 LSB/step

Depress control for fine resolution

Resolution

Fine

1 LSB/step

Setting Range

0-100% of rating

KLP will automatically adjust limit to maintain 1200W maximum

Power Up

Voltage

Defaults to zero

Last setpoint values may be saved for voltage and current

prior to unit shutdown, and recall them when unit is next turned on

Settings

Current

Defaults to min value

Protection

Overvoltage

20-120% of E

max

Programmable; accessed via front panel

protect switch or SCPI command over digital bus

Limits

Overcurrent

72-120% of I

max

KLP/KLR PROGRAMMING CHARACTERISTICS - DIGITAL

SPECIFICATION

RATING/DESCRIPTION

CONDITION

Supported

Standard

GPIB and RS 232

Supports SCPI command set for

Interfaces

Models

GPIB and RS 232

E-Series

GPIB and LAN

Support SCPI command set for

Models

Support four interfaces for LAN:

GPIB and LAN

Web interface, port 80

SCPI Telnet, port 5024

SCPI Sockets, port 5025

VXI 11, port 1024

GPIB

GPIB address range: 1 to 30

Factory default is 6

RS 232

Standard

Baud rate range: 2400, 4800,

Factory default is 38,400

Models Only

9600, 19,200 or 38,400

Digital Remote

Isolation

Safety Extra Low Voltage (SELV)

Control

Format

Compatible with SCPI protocols

W98 SE and later operating systems

Programming Resolution

0.024% of E

max

and I

max

Programming Accuracy

0.05% of E

max

and I

max

Readback Resolution

0.024% of E

max

and I

max

Readback Accuracy

0.1% of E

max

and I

max

Status Reporting

OVP, OCP, OTP, Output Lead Fault (OLF),

fan failure, source power loss

KLP/KLR PROGRAMMING CHARACTERISTICS - ANALOG

SPECIFICATION

RATING/DESCRIPTION

CONDITION

Analog Remote

Selection

Activate with jumper at analog

Recognized during power up

Control

programming connector

Isolation

Safety Extra Low Voltage (SELV)

Analog Input

2Hz (0.5 Second) applies to programming by

Analog input voltage digitized (12-bit resolution), optically

Update Rate

voltage/resistance and readback specifications

isolated, then processed by digital section

Programming

Voltage

0-10V

Voltage equivalent to Full Scale

By Voltage

can be reduced by the user

Current

0-10V

See Model Table for minimum programmable current.

Voltage equivalent to Full Scale can be reduced by the user

Programming

Voltage

0-10K ohms

Resistance equivalent to Full Scale

By Resistance

can be reduced by the user

Current

0-10K ohms

See Model Table for minimum programmable current.

Resistance equivalent to Full Scale can be reduced by the user

Readback

0-10V proportional signal

Proportional to analog control voltage/resistance

Remote inhibit

TTL compatible

Dual polarity, can be active (inhibit

the output) for either a TTL high or low

Composite Status Flag

Isolated form C contacts

Programmable. Flags system fault.

Additional user selectable flag: a) transition from CV to CC mode

or b) transition from CC to CV mode.

Advertising