Pcr-l series, Multi purpose ac power supply (cv·cf), Functions<expansion – Atec Kikusui-PCR500L User Manual

Page 6

Advertising
background image

Page6

Copyright © 2002 KIKUSUI ELECTRONICS CORP. All rights reserved.

http://www.kikusui.co.jp/

Functions<EXPANSION>

The function of the PCR-L series can be further expanded

to include measurement and output waveform genera-
tion functions through the use of an optional remote
controller and interface boards.

Note:

: Requires use of RC02-PCR-L remote controller

: Requires use of IB11-PCR-L interface board

: Requires use of RS11-PCR-L interface board

User Defined Waveform Output

3

(RS11-PCR-L / IB11-PCR-L)

/

This function allows output of data
after converting the numerical data
from a personal computer. This al-
lows output of arbitrary waveforms,
such as distortion waveforms includ-
ing harmonic components.

T1:Voltage fluctuation starting time

0 to 360deg

1deg

0 to 999.9ms

0.1ms

T2:Slope time

0ms to 9999ms

1ms

0.00s to 99.99s

0.01s

T3:Pop/Dip time

0.0ms to 999.9ms

0.1ms

0ms to 9999ms

1ms

T4:Slope time

0ms to 9999ms

1ms

0.00s to 99.99s

0.01s

T5: Power restoration time

0ms to 9999ms

1ms

0.00s to 99.99s

0.01s

0 to 9999 cycles

1cycle

0 to 99990 cycles

10cycle

0 to 999900 cycles 100cycles

V(T3): Pop/Dip voltage

0.1V

RPT

1 time

Within rated
output voltage

Setting

Resolution

Item

Setting Range

1

Power Line Irregularity Simulation Function

or

/

This function allows generation of sudden power failure, voltage fluc-
tuation, pulse superposition and other waveforms simply by setting
an arbitrary numerical value for the available parameters. It can be
used for simulation of production line evaluation and testing of power
supply irregularities in tested equipment.

Interface Boards
(For GPIB interface : IB11-PCR-L)
(For RS-232C interface: RS11-PCR-L)

AC100V 50 Hz
T1: 90 deg (5ms)
T2: 0
T3: 0.5 ms
T4: 0
T5: 0
V (T3): 0 V

0 to 9998 times
or infinity

2

Special Waveform Output

or

/

This function allows the power
supply to output waveforms for
which the peak of the sine wave is
suppressed. This can be set to a
crest factor value of 1.10 - 1.40
(resolution : 0.01)
Crest factor value = peak value /
rms value

Remote Controller (RC02-PCR-L)

T1

N or T5

(T3)

V

T1

T2

T3

T4

N or T5

P/D

INT

PCR-L series

MULTI PURPOSE AC POWER SUPPLY (CV·CF)

Advertising