Using both main and auxiliary outputs, Control modes, 2 control modes – B&K Precision 1900-1901-1902 - Manual User Manual

Page 14

Advertising
background image

12

4.1.4 Using Both Main and Auxiliary Outputs

The power supply has a main output in the rear and an auxiliary output in the front
that can be used separately or together.

The main and auxiliary output both share the same voltage and current control knobs
and will output the same voltage and current up to the maximum output ratings of
the power supply and terminals. When using both the main and auxiliary outputs
together, the power supply will automatically total the currents supplied to both
terminals up to the current limit of the power supply and show the total current on
the display.

For example, setting the voltage and current outputs for model 1900 (1-16 V, 0-60 A)
to 16 V and 60 A would output 16 V at both main and auxiliary terminals and allow
you to draw up to a total of 60 A between the two terminals. If there is a 5 A load at
the auxiliary terminal, the most current you can draw from the main output is 55 A.

If the power supply reaches its set current limit at any time, the power supply will go
into CC mode and the loads together will draw up to the total value of the current
limit. Distribution of current between the main and auxiliary terminals will vary
depending on the loads.

Note: 1900: Total rated current (Aux. + Main) is 60 A

1901: Total rated current (Aux. + Main) is 30 A
1902: Total rated current (Aux. + Main) is 15 A

4.2

Control Modes


There are four different control modes for the power supply:

Normal

Preset

Set

Remote Control

To select a mode, slide the Mode Selection Switch on the rear of the unit.

Advertising