Dialight SafeSite LED Emergency Bulkhead - ATEX/IECEx User Manual

Page 2

Advertising
background image

Dialight – LED Solutions for Industrial and Hazardous Applications

Tel: +44 (0)1638 665161 – Fax: +44 (0)1638 660718 –

www.dialight.com

Figure 1. Dimensions in mm [inches] (shown with flush mount bracket)






























=



Electrical Connections

The terminal block is suitable for multi-stranded and single
core cables up to a maximum of 4mm

2

, strip length 10mm


The LIVE (L1 and L2), NEUTRAL and EARTH connections
are clearly marked on the terminal block.

The L1 connection is a permanent live feed. It powers the
main normal mode operation, battery charger and is used to
activate emergency mode.

The L2 connection is a switched live feed to control luminaire
normal mode on or off. It is a signal input that consumes
negligible current.

Single Luminaire Electrical Connections:-

Push down at the ‘cross point’, insert correct cable and
release, ensuring the cable has been securely retained.

Loop Thru Electrical Connections:-

Connect incoming cable as above then connect the outgoing
cable to the associated adjoining connection to pass to the
next luminaire.

ONLY SINGLE CABLES TO BE USED ON EACH
CONNECTION.

L = LIVE / BROWN
N = NEUTRAL /BLUE
E = EARTH / GREEN & YELLOW

EXTERNAL BONDING EARTH ON BODY

LIVE2 (SW)
LIVE1 (PERM)

NEUTRAL

EARTH

OPTIONAL M6
EARTH BOND
POINT

Figure 2. Electrical Connection