Document No: 9100-127-1485-99 Rev A


Page 3 of 5

Exning Road, Newmarket, Suffolk, CB8 0AX, UK

Tel: +44 (0) 1638 666541 Fax: +44 (0) 1638 561735 www.dialight.com

Pendent Mount Installation Steps:

For maximum long term reliability and light output, the light must be installed in free air.

The Low Bay fixture design incorporates an over-temperature control circuit that reduces
input power should internal temperatures reach a maximum level. As a result, light output
may be reduced.

The Low Bay fixture is fitted with a 3 metre long cable that can be extended if required.

Eyebolts or other suitable fixings with an M6 thread can be secured to the rear of the High
Bay fixture for pendent mounting.

Stirrup Mounting

When the Low Bay fixture is purchased with the optional ‘Stirrup Bracket’, the luminaire
must be installed in free air.

The ‘Stirrup Bracket’ is fixed into place by the 2 bolts along the side of the light fixture,
when secured into the desired position the 2 bolts should be tightened to 8.0 – 10.0Nm.

Electrical Connection

Note: Proper electrical and installations of extension should be carried out by a qualified
electrician.

Connect power cable conductors as follows:

o

GREEN/YELLOW wire connects to Safety Ground.

o

BLUE wire connects to Neutral

o

BROWN wire connects to Live

Restore power and verify operation.

Interfacing to a PIR or Occupancy Sensor:

The Dialight Low Bay fixture is ideally suited for control by an occupancy sensor in order to
maximize energy savings based on its instant-on behavior and low power consumption.
Instructions for connecting the High Bay fixture to an occupancy sensor are listed below.

Warning:

To be installed and/or used in accordance with appropriate electrical codes and regulations.

Warning:

Controlling a load in excess of the specified ratings of the occupancy sensor could damage the unit
and pose risk of fire, electric shock, personal injury, or death. Check load ratings to determine the
unit’s suitability for your application.

NOTE: See PIR/Occupancy sensor installation instructions for additional information.

1) WARNING: TO AVOID FIRE AND ELECTRICAL SHOCK, TURN OFF POWER AT

CIRCUIT BREAKER OR FUSE AND TEST THAT THE POWER IS OFF BEFORE
WIRING.