MECHANICAL DIMENSIONS:




























ATEX/IECEx Certifications

Zone 1&21

Zone 2 &22

Ex d e mb IIB T4 Gb
Ex tb IIIC T135c Db IP66
Ex II 2 GD

Sira 12 ATEX1215
IECEx SIR 12.009

LED Enclosure rated for EXd
LED Driver Enclosure rated for Exe
LED Driver is rated for EXm

No alternate supplier materials can be
used with luminaire

Electrical Connections/Color Code

The terminal block is suitable for multi-stranded and
single core cables up to a maximum of 12gauge or
(4mm

2

) recommended strip length of .4 inches or

(10mm)

L1 = LIVE / BLACK
N = NEUTRAL / WHITE
E = GROUND / GREEN


Loop thru Electrical Connections:-

Connect incoming cable as above then connect the
outgoing cable to the associated adjoining connection to
pass to the next luminaire.


ONLY SINGLE CABLES TO BE USED ON EACH
CONNECTION.