Pendent Mount Installation Steps:

For maximum long term reliability and light output, the light must be installed in free air.

o

The High Bay fixture design incorporates an over-temperature control circuit that
reduces input power should internal temperatures reach a maximum level. As a
result, light output may be reduced.

The High Bay fixture is threaded for 3/4” NPT in order to be assembled to conduit.

o

Calculate and measure required conduit length.

o

Feed the power cable through the conduit and into the junction box.

o

Attach the fixture to the conduit (using pipe sealant).

o

Insert 1/4-20 set screw in order to secure the fixture to the conduit.

Connect power cable conductors as follows:

o

For single phase (347 VAC):

Green wire connects to Safety Ground.
White wire connects to Neutral
Black wire connects to Live

o

For two phase (480 VAC):

Green wire connects to Safety Ground.
Black wire connects to Line 1.
White wire connects to Line 2.

Restore power and verify operation.