12. Troubleshooting

Common Problems



Table 12.1, Problems, Causes, & Solutions

Problem Possible

Cause

Solutions


Frosted evaporator coil, low
suction pressure


Restricted air flow
Low fan speed
Reversed blower rotation
Low refrigerant charge


Clean, or replace filters
Check fan drives
Correct wiring
Add refrigerant

Unit runs, but supplies warm air

Loss of refrigerant
Dead expansion valve element
Plugged filter-drier

Check leaks, add refrigerant
Replace valve element
Replace filter-drier

Compressor starts, but opens
high pressure control

Refrigerant over-charged
Air in condenser coil
Condenser fan dead
Condenser coil dirty

Remove some refrigerant
Evacuate and recharge refrigerant
Replace fan motor
Clean condenser coil

High suction pressure, but low
superheat

Oversized expansion valve
Poor sensing bulb location
Low superheat adjustment

Replace with correct expansion valve
Relocate sensing bulb, secure to suction line
Adjust expansion valve

Unit operates continuously

Low refrigerant charge
Unit undersized

Check and recharge to nameplate
Decrease load or resize unit
Thermostat set too low, increase temperature setting


Compressor Checkout

Poor Cooling - Compressor Runs or Cycles

















36

High Head

Pressure

Low Head,

High Suction

Pressure

Low Suction

Pressure

Defective Compressor Valves

Bad Expansion Valve Power Element

Poor Airflow at Evaporator

Low Refrigerant Charge

Restriction in Feeder Tube

Dirty Condenser Coil (Low Airflow)

Poor Airflow at Condenser

Refrigerant Overcharge

Air in Refrigerant Circuit

Replace

Compressor

Diagnose &

Repair

Diagnose &

Repair