No cooling – compressor will not run – AAON M1-011 User Manual

Page 37

Advertising
background image

37

No Cooling – Compressor Will Not Run








































No Power to

Contactor

Power to

Contactor,

All 3 Legs

Transformer Open

Stuck Compressor

Grounded Winding

Motor Winding Open

High Pressure Switch Open

Control Panel Not Set for Cooling

Thermostat Not Calling for Cooling

Low Pressure Switch Open

Power to

Unit

No Power

Unit

Check Unit Fuses

and Windings

Check Circuit

Breaker at Power

Distribution Panel

Compressor Low Ambient Lockout Open

(Temperature Outside Below 55

°F)

Broken or Loose Control

Contactor

Open

Contactor

Closed

No 24 Volt Power to

Holding Coil

Compressor

Hums

24 Volt Power to

Holding Coil

Holding Coil

Burned Out

Replace

Contactor

Compressor Does

Not Hum

Reverse Leads

Compressor Runs

Compressor Does

Not Run

Power to

Compressor,

All 3 Legs

No Power to
Compressor

Broken Leads

Replace Leads

Motor Winding Open

Internal Overload Open

Replace

Compressor

If Compressor Dome Is

Hot, Then It May Be

Locked Out on Internal

Overload. Wait for

Reset. It Could Take

As Long As 2 Hours.