Part 3 - keypad configuration – Dynasonics MFX Series Insertion MagProbe Flow Meter User Manual
Page 52

Rev. 01/11
-3.18-
MFX
TOTAL -- Totalizer Mode
NET
POS
NEG
BATCH
Select NET to display the net difference between the positive
direction and negative direction totalizers. Select POS to only view
the positive direction totalizer. Select NEG to only view the negative
direction totalizer. Select the BATCH totalizer to configure the
totalizer to count up to a value that is entered as BTCH MUL
(described on the following page). After reaching the BTCH MUL
value, the display will return to zero and will repeat counting to the
BTCH MUL value.
SCN DWL -- Display Scan Dwell Time
1-10
Seconds
Adjustment of SCN DWL sets the time interval that the display will
dwell at RATE and then alternately TOTAL values. This adjustment
range is from 1 second to 10 seconds.
BTCH MUL -- Totalizer Batch Quantity
If BATCH was chosen for the TOTALIZER DISPLAY MODE, a value
for batch accumulation must be entered. This is the value that the
totalizer will accumulate to before resetting to zero and repeating
the accumulation. This value includes any exponents that were
entered in the BASIC menu as TOTAL E. For example:
x
If BTCH MUL is set to 1,000, RATE UNT to LITERS and TOTL E
to E0 (liters
1); the BATCH totalizer will accumulate to 1,000
liters, return to zero and repeat indefinitely. The totalizer will
increment 1 count for every 1 liter that has passed.
x
If BTCH MUL is set to 1,000, RATE UNT to LITERS and TOTL E
to E2 (liters
100); the BATCH totalizer will accumulate to
100,000 liters, return to zero and repeat indefinitely. The totalizer
will only increment 1 count for every 100 liters that has passed.
PART 3 - KEYPAD CONFIGURATION
Totalizer
Display Mode
Rate/Total
Scan Time
Displaying
Batch
Total