Incidents and solutions, 2 incidents and solutions – DE DIETRICH ALEZIO AWHP-V220 User Manual

Page 27

Advertising
background image

6.2

Incidents and solutions

Problem

Probable causes

Solution

The radiators are cold.

The heating temperature

setting is too low.

4

Increase the value of parameter d or, if a room thermostat

is connected, increase the temperature.

¼See chapter: "Modifying the set room

temperature d", page 16.

The heating mode is

deactivated.

4

Activate the heating mode.

¼See chapter: "Changing the operating mode",

page 17.

The radiator valves are closed. 4

Open the valves on all radiators connected to the heating

system.

The heat pump is not operating.

4

Check that the heat pump is switched on.

4

Check the fuses and switches on the electrical installation.

The water pressure is too low (<

1 bar).

4

Top up the installation with water.

¼See chapter: "Top up the installation with

water", page 23.

There is no domestic hot

water.

The DHW temperature setting

is too low.

4

Increase the value of parameter r.

¼See chapter: "Modifying the domestic hot water

temperaturer", page 16.

The domestic hot water mode is

deactivated.

4

Activate the DHW mode.

¼See chapter: "Changing the operating mode",

page 17.

The energy-saving shower

head is restricting the water

flow.

4

Clean the shower head; replace if necessary.

The heat pump is not operating.

4

Check that the heat pump is switched on.

4

Check the fuses and switches on the electrical installation.

The water pressure is too low (<

1 bar).

4

Top up the installation with water.

¼See chapter: "Top up the installation with

water", page 23.

Significant variations in

domestic hot water

temperature

Insufficient water supply

4

Check the water pressure in the installation.

4

Open the valve.

The heat pump is not

working.

The heating temperature

setting is too low.

4

Increase the value of parameter d or, if a room thermostat

is connected, increase the temperature.

¼See chapter: "Modifying the set room

temperature d", page 16

The heat pump is not operating.

4

Check that the boiler is switched on.

4

Check the fuses and switches on the electrical installation.

The water pressure is too low (<

1 bar).

4

Top up the installation with water.

¼See chapter: "Top up the installation with

water", page 23.

An error code appears on the

display.

4

Correct the error if possible.

¼See chapter: "Error codes", page 25.

The water pressure is too

low (< 1 bar).

Not enough water in the

installation.

4

Top up the installation with water.

¼See chapter: "Top up the installation with

water", page 23.

Water leak.

4

Contact the fitter.

AWHP-V220

6. Troubleshooting

23/04/2013 - 300026802-001-03

26