FAIL. PAC V4V

x

x

4-way valve fault
PAC malfunction
Fault level: temporary

- 4-way valve blocked open or closed
- Reversal of the heating flow and return
- Lack of refrigerant
- Regulator faulty

FAIL. PAC PUMP

x

Fault level: Permanent /
temporary

- No water
- Circulating pump breakdown

FAIL.EXT.S.PAC

x

Fault level: permanent in hot
mode / temporary in cold mode

- Opening or short circuit on the outside temperature

sensor

FAIL.RET.S.PAC

x

x

Fault level: Permanent

- Opening or short circuit on the water inlet temperature

sensor

FAIL. PAC FLOW S.

x

x

Fault level:Permanent

- Opening or short circuit on the water outlet

temperature sensor

FAIL.BAT.S.PAC

x

Fault level:Permanent

- Opening or short circuit at the fin tube exchanger

refrigerant temperature sensor

FAIL.EXCH.S.PAC

x

Fault level: permanent in cold
mode / temporary in hot mode

- Opening or short circuit of the refrigerant temperature

sensor at the heat exchanger inlet

HGAS S.HP FAIL

x

Fault level:Permanent

- Opening or short circuit of the refrigerant temperature

sensor at the compressor outlet

FLOW FAIL. 6

x

Fault level:Permanent /
temporary

- Exchanger frozen

FLOW FAIL. 7

x

Fault level:Permanent /
temporary

- Exchanger frozen

FLOW FAIL. 8

x

Fault level: temporary

- Exchanger frozen

FAIL.EEPROM CPU

x

Error EEPROM CPU

- Switch off PAC and start up again
- Change the micro-connect board

FAIL. UNKNOWN

x

Fault unknown

- Switch off PAC and start up again
- Change the micro-connect board

MC COM.FAIL

x

x

Communication fault Boiler
Module

BIOS FAIL.

x

Wrong Carel box

- Replace the box

CONFIG.FAIL.

x

Wrong coding resistor / cold
sensor combination

- Check the wiring and the cold sensor

SHUNT/CA FAIL.

x

If the contact is open and there
is a communication with the
control panel, the PAC stops
(except ROE-H)

COND. ANTI. F.

x

The PAC flow temperature is too
low

- Check that the back-ups are working

DEFROST FAIL.

x

-

AIR IN S.FAIL

x

- Opening of or short circuit on the air inlet temperature

sensor

HGAS S.FAIL

x

- Opening of or short circuit on the hot gas temperature

sensor

EVA.S.HP FAIL

x

- Opening of or short circuit on the evaporator

temperature sensor

COND.S.HP FAIL

x

-

HP FAIL.: ...

x

Fault number if this is not
included in the list

-

Display

ROE-II

ROE-H

ROE+

ROE+TH

SOLO
NAPO

ROI+

Installation malfunction/HP or

PAC

Meaning / Cause (listed in order of likelihood)



When a fault is displayed followed by AUTO, this disappears automatically after a few minutes. When the fault displayed is followed by
MANU, it is necessary to reset the HP using the reset button (See section 3.1).