8. Troubleshooting

8.2 Error messages

8.2.1

Control panel B3

In the event of a fault, the display may show the following messages:

8.2.2

Control panel K3

No error messages displayed.
See DIEMATIC-m3 control panel display.

Message

Faults

Probable causes

Action

AL 50

Boiler sensor

The sensor circuit has been broken or
short circuited.

The installation is stopped.
Advise the installer.

AL 52

Domestic hot water sensor

The sensor is cut

The installation continues to operate but domestic hot
water heating is no longer covered.
Advise the installer.

AL td

Titanium anode

The titanium anode is on an open
circuit or the tank is empty.

Production of domestic hot water is stopped. This may be
reactivated for 24 hours by disconnecting and
reconnecting the power supply to the boiler.
Advise the installer.

AL tc

A short circuit has occurred on the
titanium anode or connection
reversed.